Abstract
Neutral to Earth Voltage (NTEV) rise on the
commercial building can be categorized as one of the power
quality (PQ) problems due to abnormal load, nonlinear load,
poor grounding, and improper wiring. This paper presents the
modelling of NTEV on the commercial building considering the
magnitude and patterns of waveform using RLC circuit models
and current injection method. The current injection and RLC
circuit model are represented as a load distribution board and
grounding electrode system on the commercial building
respectively. Pearson correlation coefficient is utilized in order
to validate the rate of accuracy on simulation model. According
to the simulation, RLC grounding system produces the results
which highly correlated as compare to the actual measurement.
Metadata
Item Type: | Article |
---|---|
Creators: | Creators Email / ID Num. Mat Yusoh, Mohd Abdul Talib mohd.abdul.talib@gmail.com Abidin, Ahmad Farid UNSPECIFIED Mat Yasin, Zuhaila UNSPECIFIED |
Subjects: | Q Science > QC Physics > Electricity and magnetism > Electricity |
Divisions: | Universiti Teknologi MARA, Shah Alam > Faculty of Electrical Engineering |
Journal or Publication Title: | Journal of Electrical and Electronic Systems Research (JEESR) |
UiTM Journal Collections: | UiTM Journal > Journal of Electrical and Electronic Systems Research (JEESR) |
ISSN: | 1985-5389 |
Volume: | 11 |
Page Range: | pp. 21-28 |
Keywords: | Neutral to Earth Voltage (NTEV), Power Quality, Neutral Current, Current injection, Pearson Correlation coefficient |
Date: | December 2017 |
URI: | https://ir.uitm.edu.my/id/eprint/63011 |