Field study on the analysis of cooling load in PTAR library

Haneefa, Muhammad Ariffadhillah and Hussin, Norasikin and Suhaimi, Muhammad Syihabuddin and Abd Razak, Azli (2017) Field study on the analysis of cooling load in PTAR library. In: International Innovation & Design in Library & Information Science Compelition. Universiti Teknologi MARA, Kedah, Universiti Teknologi MARA, Kedah, p. 60. ISBN 9773030607006

Official URL: https://infomgtkdh.wixsite.com/indelib/publication

Abstract

Energy consumption is the biggest issues in commercial sector such as government office, educational building and so on. The library building is important in educational building. The function of the library is to provide the information which supports lifelong learning and continuing education for students. Commonly, the air conditioning is higher consumer energy consumption in commercial sectors. A field study was conducted in library building as known as Perpustakaan Tun Abdul Razak (PTAR UiTMCPP). The objective of this project is to identify factors that contribute to energy usage and to analyse the percentage of energy saving. The set of questionnaires has distributed to 300 respondents and interviews were conducted to find out the level of satisfaction of library conditions. The results show that 63% respondents reported feeling uncomfortable becauseof the higher cooling load. Based on the observation, the resetting cooling load is required follows the ASHRAE Standard 55. The Integrated Environmental Solution <Virtual Environment> (IES <VE>) software is used to identify the percentage of reducing electricity consumption. The IES <VE> software can give a specific data of the building energy consumption. The setting cooling load, 17ºC and resetting 24ºC has been analysed using IES <VE>. The result from IES <VE> is given that energy consumption for cooling is reduced by at least 44.77% per year when the set point temperature changed from 17°C to 24°C. Findings of this field study are useful in air conditioning system with energy savings for PTAR UiTMCPP.

Metadata

Item Type: Book Section
Creators:
Creators
Email / ID Num.
Haneefa, Muhammad Ariffadhillah
UNSPECIFIED
Hussin, Norasikin
norasikin245@uitm.edu.my
Suhaimi, Muhammad Syihabuddin
UNSPECIFIED
Abd Razak, Azli
azlirazak@uitm.edu.my
Subjects: Z Bibliography. Library Science. Information Resources > University and college. Academic libraries
Z Bibliography. Library Science. Information Resources > Library buildings. Library architecture
Divisions: Universiti Teknologi MARA, Kedah > Sg Petani Campus > Faculty of Information Management
Page Range: p. 60
Keywords: Library, Air conditioning, Cooling load, Energy saving
Date: 2017