Design and simulation of a PWM based phase synchronous inverter for utility grid systems with 20km feeder line / Tawfikur Rahman, S. M. A. Motakabber and M. I. Ibrahimy

Rahman, Tawfikur and Motakabber, S. M. A. and Ibrahimy, M. I. (2017) Design and simulation of a PWM based phase synchronous inverter for utility grid systems with 20km feeder line / Tawfikur Rahman, S. M. A. Motakabber and M. I. Ibrahimy. Scientific Research Journal, 14 (2). pp. 17-34. ISSN 1675-7009

Official URL: https://srj.uitm.edu.my/

Abstract

In recent years, the utility grid system is more essential for the power
transmission and distribution system because it cannot produce harmful
gases or no discharge waste in the environment. PWM based phase
synchronous invert systems are generally utilised in the high efficiency
energy supply, long distance and higher power quality. The inverter output
voltage depends on the coupling transformer, input sources and invert
controllers. An inverter using a three leg IGBT has been designed for utility
grid and simulated by using MATLAB2014a. In this paper, both sides of
the LCL filters are used for removing the DC ripple current, reducing the
noise and synchronous the output phase between inverter and the utility
grid. The PWM controller has created pulse signal to control the inverter,
electronic switches and precisely synchronise with grid line frequency. In
this system, the input DC voltage 500V, switching frequency 1.65 kHz, grid
frequency 50Hz, 20 km feeder (resistance, inductance and capacitance per
unit length, which are 0.1153, 1.05e-3 and 11.33e-09 ohms/km) with 30MW
three phase load (active and inductive reactive power which are 30e6
W
and 2e6 var) and also a balanced utility grid load of star configuration (00
,
1200
, and 2400 degree) are considered in the design. On the other hand,
three phase transformer consists of three signal phase transformers, normal
power 100e3
, magnetization resistance and inductancewhich are 500 pu and
416.67pu are considered in this design. The system conversion efficiency
is 99.94% and 99.96%, while the total THD are 0.06% on inverter side
and 0.04% on grid side.

Metadata

Item Type: Article
Creators:
Creators
Email / ID Num.
Rahman, Tawfikur
UNSPECIFIED
Motakabber, S. M. A.
UNSPECIFIED
Ibrahimy, M. I.
UNSPECIFIED
Subjects: T Technology > TK Electrical engineering. Electronics. Nuclear engineering > Applications of electric power
Divisions: Universiti Teknologi MARA, Shah Alam > Research Management Centre (RMC)
Journal or Publication Title: Scientific Research Journal
UiTM Journal Collections: UiTM Journal > Scientific Research Journal (SRJ)
ISSN: 1675-7009
Volume: 14
Number: 2
Page Range: pp. 17-34
Keywords: PSI, controller, LCL filter, transformer and feeder